♦ Types of surge suppressed:
Lightning Flash Surges (LFS), Power switching surges (PSS), Switching Inrush Current (SIC), and Electric Magnetic Pulse (EMP).
♦ Method of handling surge energy:
Series mode surge energy absorbed and transferred to voltage.
♦ Case of Devices:
Metal structure case with anode treatment and sand blasting to prevent EMI interference of itself.
♦ Suitable AC voltage:
400V(L-L), 220 V-300V (L-N) ±5%, 50/60Hz.
♦ Max. load current allowed:
15A (L-N).
♦ Input Impedance (R) without loads:
>10MΩ.
♦ Temperature of case under 15A load:
Less than 55 oC.
♦ Surge immunity:
1.2x50μs,20kV; 8x20μs,10kA combination wave, 60 sec interval, at least 3times.
♦ Surge energy absorbing rate:
1.2x50μs,20kV; 8x20μs,10kA combination wave, 97%±1.
♦ After surge invasion, AC waveform recovering time:
Less than10mS.
♦ After surge invasion, AC waveform correction ability:
1-3A load condition, more than 3 cycles.
♦ EMP(fast transient/bust) immunity:
4.5kV, 5x50ns EFT waveform, 95%±2% (ungrounding condition).
♦ Loads remnant voltage:
Less than 660V±20% (L-N and N-G), 1,040V±20% (L-L) under combination wave tested.
♦ Load protection mode:
L-L, L-N, and L-G.
♦ System ground resistance demand:
None.
♦ Operation temperature range and humidity range:
-40 to +85oC, 35 to 95% relative humidity (no dew).
♦ Dimension:
Base 116mm (L)×94mm(W)/ Cover 116mm (L)×94mm(W)×30mm(H) ±1%.
♦ Weight:
Less than 378g ±5%.
♦ Confirm standards:
ANSI C62.41、IEC 61000-4-5、IEC 61000-4-4、IEC 61643-1、ANSI C37.90.1etc.
♦ Surge-testing:
On-line condition, tested by10kV/5kA combination wave, 4.5kV, 5x50ns EFT wave.