Model: | - |
---|---|
Brand: | BAOSHIDA |
Origin: | Made In China |
Category: | Electronics & Electricity / Optical Fiber, Cable & Wire / Electric Wire & Cable |
Label: | Nuclear power cable , BAOSHIDA , manufacture |
Price: |
US $80
/ meter
|
Min. Order: | 1 meter |
Application:
The product is authorized as per the standard of RCC-E and IEE383 to use for exterior cable in the nuclear power station and other locales where there is high requirements for electric physics flame resistance of cables.
Type and Name:
Type |
Name |
HEJE-K3 |
Cross-linked polyolefin insulated PO sheathed LSOH flame-retardant power cable for nuclear power stations |
HKEJE-K3 |
Cross-linked polyolefin insulated PO sheathed LSOH flame-retardant control cable for nuclear power stations |
HKEJEP-K3 |
Cross-linked polyolefin insulated PO sheathed LSOH copper braided shielded flame-retardant control cable for nuclear power stations |
HKEJEP2-K3 |
Cross-linked polyolefin insulated PO sheathed LSOH copper strip shielded flame-retardant control cable for nuclear power stations |
HKEJEP3-K3 |
Cross-linked polyolefin insulated PO sheathed LSOH ELE shielded flame-retardant control cable for nuclear power stations |
HKEJEP3P-K3 |
Cross-linked polyolefin insulated PO sheathed LSOH ELE and copper braided shielded flame-retardant control cable for nuclear power stations |
HDJEJEP-K3 |
Cross-linked polyolefin insulated PO sheathed LSOH copper braided shielded flame-retardant measuring cable for nuclear power stations |
HDJEJEP2-K3 |
Cross-linked polyolefin insulated PO sheathed LSOH copper strip shielded flame-retardant measuring cable for nuclear power stations |
HDJEJEP3-K3 |
Cross-linked polyolefin insulated PO sheathed LSOH ELE shielded flame-retardant measuring cable for nuclear power stations |
HDJEJEP3P-K3 |
Cross-linked polyolefin insulated PO sheathed LSOH ELE and copper braided shielded flame-retardant measuring cable for nuclear power stations |
HDJEJPE-K3 |
Cross-linked polyolefin insulated PO sheathed LSOH copper braided pair twist shielded flame-retardant measuring cable for nuclear power stations |
HDJEJPEP-K3 |
Cross-linked polyolefin insulated PO sheathed LSOH copper braided pair twist and collectively shielded flame-retardant measuring cable for nuclear power stations |
HDJEJP2EP2-K3 |
Cross-linked polyolefin insulated PO sheathed LSOH copper strip pair twist shielded flame-retardant measuring cable for nuclear power stations |
HDJEJP3E-K3 |
Cross-linked polyolefin insulated PO sheathed LSOH ELE pair twist shielded flame-retardant measuring cable for nuclear power stations |
HDJEJP3EP3-K3 |
Cross-linked polyolefin insulated PO sheathed LSOH ELE pair twist and collectively shielded flame-retardant measuring cable for nuclear power stations |
Operating Properties:
1、Max. permissible continuous operating temperature of conductor: Not exceeding 90℃.
2、Max. temperature of conductor will not exceed 250℃ when short-cut(in 5 seconds).
3、The temperature when laying the cable should not below 0℃.
4、Insulated with
5、The density for braided copper screen should be no smaller than 80%.
6、The thermal life for cable should confirm to the requirement that the cable life should be no less than 40 years.
7、Finished cables should pass the test of bundling burning test of Class B specified in GB/T18380.3-2001.
8、Smoke density of finished cables’ burning test should confirm to the requirements of GB/T17651.
9、Release air test for finished cables’ insulation and sheath should confirm to the requirements of GB/T17650.2.
Range of Production:
Type |
Number of cores |
Nominal cross sectional area mm2 |
HEJE-K3 |
2~5 |
1.5~300 |
HKEJE-K3 |
2~37 |
0.5~2.5 |
HKEJEP-K3 |
||
HKEJEP2-K3 |
||
HKEJEP3-K3 |
||
HKEJEP3P-K3 |
||
HDJEJE-K3 |
||
HDJEJEP-K3 |
2cores group:2~15 pairs
|
0.75、1.0、1.5 |
HDJEJEP2-K3 |
||
HDJEJEP3-K3 |
||
HDJEJEP3P-K3 |
||
HDJEJPEP-K3 |
||
HDJEJP2EP2-K3 |
||
HDJEJP3EP3-K3 |
Max. DC Resistance of conductor at 20℃:
Nom. cross-sectional of conductor |
DC.
|
Nom. cross-sectional
|
DC.
|
Nom. cross-sectional
|
DC.
|
mm² |
copper |
mm² |
copper |
mm² |
copper |
0.75 |
24.5 |
16 |
1.15 |
150 |
0.124 |
1 |
18.1 |
25 |
0.727 |
185 |
0.0991 |
1.5 |
12.1 |
35 |
0.524 |
240 |
0.0754 |
2.5 |
7.41 |
50 |
0.387 |
300 |
0.0601 |
4 |
4.61 |
70 |
0.268 |
400 |
0.047 |
6 |
3.08 |
95 |
0.193 |
500 |
0.0366 |
10 |
1.83 |
120 |
0.153 |
-- |
-- |
Current carrying capacity of cable:
Cross-linked polyolefin insulated sheathed LSOH flame-retardant power cable for Nuclear Power Stations:
Nom. cross- sectional area mm² |
2 cores |
3 cores |
4 cores |
5 cores |
1.5 |
20 |
20 |
27 |
28 |
2.5 |
26 |
27 |
35 |
36 |
4 |
34 |
35 |
45 |
46 |
6 |
43 |
44 |
57 |
58 |
10 |
75 |
65 |
70 |
64 |
16 |
100 |
85 |
90 |
84 |
25 |
140 |
115 |
130 |
115 |
35 |
175 |
145 |
165 |
141 |
50 |
210 |
175 |
200 |
172 |
70 |
270 |
220 |
258 |
218 |
95 |
340 |
270 |
320 |
269 |
120 |
400 |
315 |
380 |
313 |
150 |
460 |
360 |
440 |
359 |
185 |
530 |
420 |
505 |
405 |
240 |
625 |
500 |
603 |
451 |
300 |
-- |
580 |
700 |
497 |
400 |
-- |
640 |
795 |
543 |
500 |
-- |
760 |
880 |
-- |
Operating conditions when laying the cable:
1、Max. operating temperature of conductor: XLPE insulated: 90℃.
2、Surrounding temperature:40℃.
Correction factors at different ambient air temperatures:
ambient air temperature |
20 |
25 |
30 |
35 |
Rating factor |
1.18 |
1.14 |
1.1 |
1.05 |
ambient air temperature |
40 |
45 |
50 |
— |
Rating factor |
1 |
0.95 |
0.89 |
— |
Product Name: Cable for Nuclear Power Station
ShanDong BaoShiDa Cable Co.,Ltd | |
---|---|
Country/Region: | Shan Dong - China |
Business Nature: | Manufacturer |
Phone: | 88681868 |
Contact: | Marina (export trader) |
Last Online: | 05 Jan, 2017 |